The Unit Of Measure For Gas Alarm Detectors

0-100% LEL and 0-n PPM in the gas alarm detector

(1) "LEL" refers to the lower explosive limit. The lowest concentration of flammable gas in the air when it encounters an open flame explosion is called the lower explosion limit—abbreviated as %LEL. English: Lower Explosion Limited.

So what is the lower explosion limit?

It is not dangerous if the concentration of flammable gas is too low or too high. It will burn or explode only when it is mixed with air to form a mixture or more precisely when it encounters oxygen to form a certain proportion of the mixture. Combustion is a violent oxidation reaction accompanied by light and heat, and it must have three elements:

a. Combustibles (gas);

b. Combustion support (oxygen);

c, ignition source (temperature).

Combustion of combustible gas can be divided into two categories

One is diffusion combustion, that is, the volatile or ejected or leaked combustible gas from the equipment will mix and burn when encountering an ignition source.


Another type of combustion is the combustion of combustible gas and air mixed with air. This combustion reaction is intense and fast, and generally produces huge pressure and sound, also known as explosion.


There is no strict distinction between burning and explosion. Authoritative departments and experts have made combustion and explosion analysis of the found combustible gas, and formulated the explosion limit of combustible gas, which is divided into upper explosion limit (UEL for upper explode limit in English) and lower explosion limit (abbreviation for lower explode limit in English). LEL). Below the lower explosion limit, the content of combustible gas in the mixture is insufficient to cause combustion or explosion, and above the upper limit, the content of oxygen in the mixture is insufficient and cannot cause combustion or explosion. In addition, the combustion and explosion of combustible gas are also related to the pressure, temperature, ignition energy and other factors of the gas. The explosion limit is generally expressed in volume percent concentration. The explosion limit is a general term for the lower explosion limit and the upper explosion limit. The concentration of combustible gas in the air will only explode when the concentration of the combustible gas is between the lower explosion limit and the upper explosion limit. No explosion will occur below the lower explosive limit or above the upper explosive limit. The measurement range of various combustible gas detectors is 0-100% LEL.


Fixed combustible gas detectors usually have two alarm points (related to the model of the alarm host): 10% LEL is a first-level alarm, and 25% LEL is a second-level alarm. Portable combustible gas detectors usually have an alarm point: 25% LEL is the alarm point. For example, the lower explosion limit of methane is 5% volume ratio, that is to say, this 5% volume ratio is divided into one hundred equal parts, so that 5% volume ratio corresponds to 100% LEL, that is, when the detector value reaches 10 When the %LEL alarm point is reached, it is equivalent to the methane content of 0.5% by volume. When the detector value reaches the 25% LEL alarm point, it is equivalent to the methane content of 1.25% by volume. Therefore, you don't have to worry about whether there is danger at any time after the alarm. At this time, it is reminding you to take corresponding measures immediately, such as turning on the exhaust fan or cutting off some valves, etc., to avoid the real possibility of dangerous explosion. There is still a big gap, so that it will play the role of an alarm prompt.


(2) ppm is the volume ratio concentration: Parts per million.

①ppm is a method of expressing the concentration of the solution (the mass fraction of the solute), and ppm means one part per million.

For solution: that is, 1/1000 ml of solute in 1 liter of aqueous solution, then its concentration (solute mass fraction) is 1 ppm.

②For gas: one of the representation methods for the concentration of pollutants in the ambient atmosphere (air).

Volume concentration notation: the volume of pollutants contained in one million volumes of air, or ppm

The gas concentration measured by most gas detection instruments is volume concentration (ppm). According to my country's regulations, especially the environmental protection department, the gas concentration is required to be expressed in units of mass concentration (eg: mg/m3), and our country's standard specifications are also expressed in units of mass concentration (eg: mg/m³;).